Water Fittings Directory

Installation Requirements

AMENDMENT NO. 8 OCTOBER 2002

 

As the incorrect installation of water fittings may result in contravention of Water Byelaws or Regulations the following INSTALLATION REQUIREMENTS & NOTES (IRNs) are intended as guides to Water Suppliers, Installers and their customers. The IRN numbers appear at the top of each entry in the Fittings section of the Directory

 

PART A

 

Previous Installation Requirements under Water Company Byelaws prior to enforcement of the Water Supply (Water Fittings) Regulations 1999 in England and Wales and the Water Byelaws 2000 in Scotland. Also applicable to Water Regulations in Northern Ireland.

 

 

IRN 000

No installation requirements or notes

 

 

IRN 001

See text of entry for installation requirements or notes

 

 

IRN 101~

Water supplies shall be at reasonably balanced pressures and taken from a common source (both from storage by gravity or both from the supply pipe).  Where the fitting is installed in domestic premises supplies may be taken from separate sources provided a ' Listed ' single check valve or some other no less effective backflow prevention device is fitted immediately upstream of both hot and cold water inlets.

 

 

IRN 103~

Multiple inlet fittings in domestic premises shall be installed in accordance with IRN 101 and with a double check valve assembly or some other no less effective backflow prevention device fitted at the connection to the shower hosepipe.  A single check valve or vacuum breaker may be fitted in place of the double check valve if single check valves are fitted at each inlet to the fitting.  Alternatively the fitting shall be supplied in accordance with IRN 109 unless the shower head is constrained above the Spill-over level of the bath, wash basin or shower tray.

 

 

IRN 104~

Multiple inlet fittings incorporating a self cancelling diverter acceptable as a backflow prevention device shall be installed in accordance with IRN 101 and, unless the shower head is constrained above the spill - over level of the bath, washbasin or shower tray shall be installed either:- 

 

(a) with a single check valve or some other no less effective backflow prevention device immediately upstream of each inlet; or

 

(b) with a single check valve or vacuum breaker fitted between the diverter and the shower head; or

 

(c) so that it draws water by gravity only from a cistern, cylinder or tank having a permanently open vent pipe, the vertical distance between the point at which the pipe or pipes supplying water to the fittings is or are connected to the supply and the spill-over level of any fixed appliances is not less than 25mm, and the pipe or pipes supply(ies) no other fitting (other than the draining tap) at a lower level.

 

 

IRN 105~

Supply shall be by gravity from a cistern, by means of a distributing pipe which does not supply any other fitting at a lower level.

 

 

IRN106~

Supply(ies) shall be via a type A air gap or from storage by distributing pipe(s) to which no fittings for other purposes are connected.

 

 

IRN 107~

Supply(ies) shall be from storage.

 

 

IRN 108~

For above ground use only on cold water services only.

 

 

IRN 109

The fitting shall be installed so that its outlet discharges above the spill-over level of any fixed appliance as indicated in the following table:-

 

 

 

If the fitting cannot be installed as indicated in the table it shall be installed:-

 

a) with a 'Listed' double check valve assembly or some other no less effective backflow prevention device immediately upstream of the inlet; or

 

b) so that it draws water by gravity only from a cistern, cylinder or tank having a permanently open vent pipe, the vertical distance between the point at which the pipe or pipes supplying water to the fittings is or are connected to the supply and the spill-over level of any fixed appliances is not less than 25mm, and the pipe or pipes supply(ies) no other fitting (other than the draining tap) at a lower level.

 

 

IRN 110~

A 'Listed' double check valve or some other no less effective backflow prevention device shall be fitted to the inlet unless the shower head is constrained above the spill-over level of the bath, washbasin or shower tray.

 

 

IRN 111~

The fitting is to be so installed as to be readily accessible for examination, repair, replacement or operation.

 

 

IRN 112~

If the shower head is not constrained above the spill-over level of the bath, wash basin or shower tray, a single check valve or some other no less effective backflow prevention device must be installed between the outlet of the fitting and the shower head, or a single check valve shall be installed at both hot and cold water inlets - Byelaw 17.  Alternatively the fitting shall be installed in accordance with IRN 109b.

 

 

IRN 113~

The fitting (s) are only acceptable for servicing purposes and when installed on a distributing pipe with a static water pressure not exceeding 1 bar.

 

 

IRN 115~

All outlet connections to cisterns, which are arranged to receive thermal expansion water, shall be fitted both internally and externally with suitably protected support washers.

 

 

IRN 116~

Sealed primary circuits and/or secondary hot water systems shall incorporate means for accomodating the thermal expansion of water to prevent any discharge from the circuit and/or system except in an emergency situation

 

 

IRN 118~

Supplies to primary and secondary circuits shall be from separate cisterns.  No boiler primary circuit shall be connected to a supply pipe.

 

IRN 119~

A 'Listed' double check valve or some other no less effective backflow prevention device shall be fitted to the inlet.

 

IRN 120~

A 'Listed' single check valve or some other no less effective backflow prevention device shall be fitted at the inlet where the fitting is connected to a supply pipe.  Water Undertakers cannot be responsible for any water quality complaints from water passed through these fittings.

 

IRN 121~

For use on the supply to one or more adjacent draw-off points only.  These devices are not suitable for use as point-of-entry units to treat the general supply of water to a building.

 

IRN 123~

The supply to the storage cistern shall be discharged via a Type A air gap.

 

IRN 124~

Plastic tubes and fittings rated for cold water use only shall not be installed where they may be subject to the effect of external heat.

 

 

IRN 125~

For closed circuit use only

 

IRN 126~

A 'Listed' single check valve or some other no less effective backflow prevention device shall be fitted at the point of connection(s) between the supply and the fitting

 

 

IRN 128~

The unit shall not be used in surgical or industrial situations unless supplied via a Type A air gap or an interposed cistern

 

IRN 129~

Certain water undertakers require the supply to this fitting/appliance to be by means of a metered supply only, as it is impracticable to determine or regulate its consumption by the imposition of design criteria

 

IRN 130~

Solder alloys containing lead shall not be used in connection with systems which convey or receive water supplied for domestic purposes.

 

IRN 131~

Where installed on domestic premises, or elsewhere with the written consent of the undertakers, the fitting shall be installed with a 'Listed' double check valve or some other no less effective device or, the fitting shall draw water by gravity only from a cistern by means of a pipe to which no other draw off tap or fitting is connected downstream (other than a draining tap) or from which water may be drawn at a lower level.

 

IRN 132~

This cistern is not suitable for storing water for domestic purposes.

 

IRN 133~

No vent, warning or overflow pipe from a primary feed cistern shall convey water to any cistern supplying water to a secondary system from which water may be drawn for domestic purposes.

 

IRN 134~

The fitting is not suitable for conveying hot water.

 

IRN 135~

A servicing valve shall be installed at every take-off from a storage cistern, hot water cylinder or tank.

 

IRN 136~

A servicing  valve shall be installed at the inlet to the fitting.

 

IRN 137~

A drinking water tap shall be provided upstream of this fitting.

 

 

IRN 140~

 

BIDETS

 

Byelaw 19 precludes the connection of rim feed or ascending spray type bidets or bidets with hand-held spray attachments to any supply pipe and Byelaw 20 covers those of over rim type feeds, specifying air gap requirements. Bylaw 21(1) lays down restrictions concerning supplies to bidets and other points of draw-off, with Byelaw 21(2) permitting certain exceptions.

 

BIDETS WITH OVER-RIM SUPPLY ARRANGEMENTS

 

(a) the requirements of Byelaws 19 and 20 would be accepted as being

Satisfied whenever a bidet is equipped with separate hot and cold taps and site verification of the air gaps confirms they are in accordance with the requirements of the table in Byelaw 16(2) – see IRN 109

 

Such air gaps can be obtained whenever draw-off taps complying with either BS 5412 or BS 5413 are installed on bidets complying with the appropriate requirements of BS 5505; part 3 “ vitreous china bidets over-rim supply only”.

 

 

Diagram 1. Over-rim type bidet

 

 

Arrangements complying with diagram 1 permit connection either to hot and cold water distributing pipes or direct to the supply pipe for cold water and to a supply pipe fed unvented heater for hot water. There are no restrictions on the taking of feeds from the distributing or supply pipes to other draw-off taps or water fittings at any level.

 

(b)  in the case of a bidet equipped with a single outlet ( single flow) mixing

Tap and side verification confirms the air gap is in accordance with the table in Byelaw 16(2) – see IRN 109 – hot and cold supplies can be provided by distributing pipes or direct from the supply pipe as described above. When the water pressures are balanced there are no restrictions on the taking of feeds from either the distributing of supply pipes to other draw-off taps or water fittings at any level.

 

If the water pressures are unbalanced , single check valves must be provided in the pipes supplying the mixer tap.

 

(c) in the case of a bidet equipped with a double outlet ( divided flow) mixing tap  the comments given in “a” for separate how and cold taps apply.

 

BIDETS WITH ASCENDING SPRAY (OR RIM FLUSH)

 

(a) the requirements of Byelaw 21 would be accepted as being satisfied when a bidet not of the over-rim feed type is connected to an unvented hot water system if the hot and cold water are supplied via a break pressure tundish or cistern which provides an air gap meeting with the requirements of the table in Byelaw 11 ( as in IRN 109)  between the supply pipe and the bidet (see diagram 2).

 

 

Diagram 2. Ascending spray type bidet

 

 

There are no restrictions on the taking of feeds to other draw-off taps or water fittings provided the connections are made upstream of the mixing valve.

 

Note: this arrangement could be used when hot and cold water is provided in distributing pipes at balanced pressures.

 

(b)  the requirements of Byelaw 21 would also be accepted as being satisfied in the following examples of balanced cistern fed systems

 

(i) water under cistern pressure is conveyed by separate distributing pipes which connect to no other tap or appliance other than a feed pipe to  a   flushing cistern (see Byelaw 21 (2) ). The hot water heater serves the bidet only (see diagram 3).

 

 

Diagram 3. Ascending spray type bidet

 

 

(ii)  water under cistern pressure is conveyed in separate distributing  pipes to the bidet. The separate hot water distributing pipe is connected above the cylinder to the vent pipe at point a and is fitted with an additional vent pipe connected to it at point b downstream of a check valve (see Byelaw 21 (2) (c) (i) Points A and B must be at least 300mm higher than the spill-over level of the bidet (see diagram 4)

 

Note: Certain types of check valve have a high head loss and if the cistern is at a low level the available pressure at the bidet may be inadequate to give a satisfactory spray.

 

 

Diagram 4. Ascending spray type bidet – with fittings at a lower level

 

In this example there are no restrictions on the taking of supplies to other points of use at any level provided the water is conveyed in distributing pipes not connected to those serving the bidet (other than cold water to a flushing cistern).

 

(iii) Water under cistern pressure is conveyed in distributing pipes to the bidet which is at the lowest point of use. The vented hot water distributing pipe and the cold water distributing pipe are both connected at least 150mm higher than the spill-over level of the bidet (see Byelaw 21 (2) (c) (i) and Byelaw 16 (3) (c). See diagram 5).

 

 

Diagram 5. Ascending spray type bidet – no fittings at a lower level

 

There are no restrictions on the taking of supplies to other points of use in that none can be any lower than the spill-over level of the bidet.

 

IRN 202~

Certain water undertakers advise that copper cylinders and tanks be fitted during manufacture with aluminium protector rods to promote resistance to corrosion.

 

IRN 203~

Certain water undertakers require aluminium covers to be protected by a 'listed' paint or lacquer.

 

IRN 204~

Certain water undertakers accept only galvanised Grade A mild steel cisterns.

 

IRN 205~

Certain water undertakers require galvanising to be coated with 'listed' protective paint.

 

IRN 208~

the installation of a new or replacement flushing cistern incorporating a dual flush facility not exceeding 9.5 litres is permitted in all premises until 1st January 1993. After 1st January 1993 no new installation of a dual flush cistern is permitted.

 

IRN 209~

Certain water undertakings do not accept galvanising as a suitable means of internal protection for fittings

 

IRN 210~

Every WC flushing cistern which gives a nominal flush exceeding 7.5 litres shall operate in the dual flush mode only, and the instructions for so operating it shall be displayed adjacent to the operating lever.

 

IRN 211~

Every float-operated valve or other device for controlling the inflow of water to a storage cistern with a capacity not exceeding 5000 litres shall be securely and rigidly fixed to that cistern and installed so that the inflow of water is shut off when the level of water in the cistern is not less than 25mm below the overflowing level of that cistern.  Where the cistern capacity exceeds 5000 litres, and a device other than a warning pipe is fitted, the shut off level of the inflow control device shall be not less than 50mm below the overflowing level.

 

 

IRN 302~

Unvented primary circuits may be filled or replenished by means of a temporary connection between the circuit and a supply pipe porvided a 'listed' double check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use

 

Fittings manufactured from duplex (alpha-beta) brass are not acceptable for underground use and certain water undertakers also restrict their use above ground.

 

WATERHAMMER AND FITTINGS WHICH CONTROL FLOW

Byelaw 54 requires every pipe to be adequately supported and secured to avoid any damage from airlock or reverberation.

Whilst there is no documentary evidence to show the magnitude and extent of waste of water in consumers’ premises as a consequence of waterhammer, there is no doubt that sudden excessive pressure rises within pipework could lead to premature failure of jointing and possible damage to connected fittings. In cases where unacceptable waterhammer occurs when particular fittings or appliances are used, suitable measures should be taken which could include the fitting of air or gas loaded vessels or special mechanical waterhammer arresters.